Programming The Gems Programmable SAFE-PAK®

Normally Open Load Operation: Switch closure to terminals 5 and 7 turns programmable Relay "on" and energises load.  Same switch opening will turn "off" programmable Relay and de-energise load.  Terminals 6 and 8 are not used.

Normally Closed Load Operation: Switch closure to terminals 6 and 7 turns Programmable Relay "off" and de-energised load.  Same switch opening will turn "on" programmable Relay and energise load.  Jumper must be connected between terminals 5 and 7... terminal 8 is not used.

Latching "A" Operation: For refill control, momentary switch closure to terminals 5 and 7 turns Programmable Relay "on" and energised load.  Load remains "on" until the Programmable Relay turns "off" with a momentary switch closure at terminals 6 and 7.  The load is then de-energised.  Jumper must be connected between terminals 7 and 8.  For pump-down, reverse wires on terminals 5 and 6.

Latching "B" Operation: Momentary switch closure to terminals 5 and 7 turns Programmable Relay "on" and energises load.  Load remains "on" until the N.C. switch terminals 7 and 8 opens.  The Programmable Relay turns "off" and load is de-energised.  Terminal 6 and jumper are not used.

Note:  Latching function should be accomplished on sensor input side of the Programmable SAFE-PAK®. No latching function is advised on the output power circuit side.

Typcial Wiring

Typical Wiring

Typical Wiring

Typical Wiring